banner banner banner banner
Our Products

TF413P VITF 24/630-16P





Electrical Ratings (3Phase) Symmetrical Basis
Rated frequency 50/60Hz
Rated Voltage 24kV,r.m.s
Rated short-time power-frequency withstand voltage (1 min) 60kV,r.m.s
Rated lightning impulse withstand voltage 125kV,Peak
Rated Current 630A
Maximum Contact Resistance at Minimum Closing Force≤35Micro ohms
Rated short-time withstand current20kA,r.m.s
Rated duration of short-circuit4s
Rated peak withstand current50kA,r.m.s
Rated short-circuit making Current50kA,r.m.s
Rated active load breaking current630A
Rated closed-loop breaking current630A
Rated capacity of no-load transformer1250kVA
Rated cable-charging breaking current10A
*Rated breaking current of single capacitor bank400A
*Rated breaking current of back-to-back capacitor bank400A

Mechanical Data
Interrupter Weight(Approx.)1.25kg
Weight of movable parts0.68kg
Closing force due to bellow and atmosphere70±30N
Force required to hold contacts open at full stroke145±50N

Mechanical Requirements (Ref. Lbs)
Clearance between open contacts12±1mm
Average opening speed(average of first 75% of contact gap)1.2±0.2m/s
Average closing speed(average of last 30% of contact gap)0.7±0.2m/s
Rated added external contact final force1000±100N
Added external contact force at contact touch point750±80N
Contact bouncing duration at closing operation≤2ms
Closing and Opening non-simultaneity of three-phase Contacts≤2ms
Maximum Rebound during opening≤2ms

Life
Storage life20years
Mechanical endurance10000 Operations
Contacts limit erosion3mm

Note
  • Meets or exceeds the electrical endurance requirements of class E2 for autoreclosing duty per IEC 62271-200 and JB 8738-2008.
  • * Rated Characteristics to be given on request"